1KV heat shrinkable termination

1KV heat shrinkable termination
Product Detailed
Related Categories:Other Wiring Accessories
It contains insulation tubes and breakouts. Its unique patented water-proof design ensures higher security of cable accessories.

Product Introduction:

1KV heat shrinkable terminations are designed for 1,2,3,4 and 5-core XLPE insulated cables. The whole set contains heat shrinkable insulation tubes and breakouts.Its unique patented water-proof design ensures the higher security of cable accessories.

As part of the termination, Heat Shrinkable Insulation Tubing is suitable for a variety of low voltage electrical and mechanical applications. It is fast and easy to install and has been proven long term reliability in harsh climatic conditions and polluted environments. Heat Shrinkable Breakouts can seal and protect multi-conductor cable and conduit breakouts.

 

Characteristics:

1.Operating Temperature:-40 degree -- 110 degree ;

2.Shrink Temperature: 90 degree ;

3.Waterproof, RoHS compliant.

 

Technical Data:

 

PROPERTY

TEST CONDITION AND TEQUIREMENT 

RESULTS

A.C. Voltage Withstand(dry withstand)

No breakdown and flashover shall occur at 4kVx1min

No breakdown and flashover occurred on the combi.sample at 4kV, 15min

A.C. Voltage Withstand(wet withstand)

No breakdown and flashover shall occur at 4kVx1min

No breakdown and flashover occurred on the combi.sample at 4kV, 1min

Impulse Voltage Withstand

10 positive and 10 negative, 8 kV peak

no breakdown and no flashover

Thermal Short Circuit

No transfigure and welding shall occur on all parts at 17.7kAx1s

No transfigure and welding shall occur on all parts at 17.7kA, 1s

DC negative polarity voltage withstand for 5 min.

no breakdown and no flashover at 15kV

no breakdown and no flashover occurred on the combi. sample at 15kV

Insulation Resistance

≥ 1000 MΩ

≥ 1000 MΩ

A.C. Voltage withstand, 4h

2.4kVx4h

Pass