10KV Indoor Heat Shrinkable Termination
Product Introduction:
10KV indoor heat shrinkable terminations are designed for 1 and 3-core XLPE power cables. The whole set contains heat shrinkable insulation tubes,stress control tubes,breakouts, sealing tubes, phase color tubes and voil filler.Its unique patented water-proof design ensures the higher security of cable accessories.
Its high permittivity material endows it unique stress control system. And with compact design and few components, this product is easy to install, minimal waste for disposal. Fast, consistent installation means lower installing costs. Installation environment: use of torch adds flexibility to cable preparation in any climate. It also has high reliability. Heat-activated seals ensure maximum protection against moisture ingress. Lightweight construction requires no additional support. UV resistant, non-tracking outer tube for long life, even under adverse conditions. It also has excellent mechanical robustness.
Characteristics:
1.Operating Temperature:-40 degree-110 degree;
2.Shrink Temperature:90 degree;
3.Waterproof, RoHS compliant.
Technical Data:
PROPERTY | TEST CONDITION AND TEQUIREMENT | RESULTS | |||
AC withstand for 1 min.(dry withstand, for indoor termination) | No breakdown and flashover shall occur at 45kV, 1min | No breakdown and flashover occurred on the combi.sample at 45kV, 1min | |||
Partial discharge | 13kV, ≤20PC | 13kV, ≤20PC | |||
Load cycle | Heating for 5h, cooling for 3h. Conductor's temperature is 95, 3 cycles | Conductor's temperature is 95. Results refer to the following test | |||
Impulse voltage withstand 1.2/50us±10times | 10 positiVe and 10 negative impulses at 105kV, flashover 1 time is allowed but not including total testing times | No breakdown of the combi.sample occurred at 105kV | |||
DC voltage withstand negative 15 min. | No breakdown and flashover shall occur at 52kV | No breakdown and flashover occurred on the combi.sample at 52kV, 15min | |||
AC voltage withstand, 4h | No breakdown and flashover shall occur at 35kV, 4h | No breakdown and flashover occurred on the combi.sample at 35kV, 4h | |||
Oil-seal up test | Heating for 24h, cooling for 24h. Conductor's temperature is 65, oil pressure: 100MPA | No leaking, no seeping | |||
(Only for Paper insulated cables) |
10KV Indoor Heat Shrinkable Termination